There's no link to the data sheet of the actual cable, but, yeah, looks like this should not have happened in such a short timeframe unless there's something really funny going on in that room, like ambient temperatures above 50 degC.
Another thing that should not have happened is installing the cable in loops in this way: any 'building' or 'underground' type cable needs to be of the exact length required at the demarcation point, fastened properly to prevent movement and terminated on a proper patch panel (can be a one-port box-type thingy for small setups), from where you use regular patch cords to connect your equipment.
(Loops are definitely allowed though, but that use case is mostly for aerial fiber to enable repair splices, and there are some very specific bend-radius and strain relief requirements, which, again should be spelled out in the cable data sheet)
> any 'building' or 'underground' type cable needs to be of the exact length required at the demarcation point, fastened properly to prevent movement and terminated on a proper patch panel (can be a one-port box-type thingy for small setups)
How exact is exact? :-) I once had to reterminate some fiber that was cut and terminated to exact length, which means there was literally two centimeters from the wall to the connector. I literally had to squeeze the fiber splicer up against the wall to have a chance at splicing on new pigtails, but I had two mis-cuts and I was hosed. :-)