Comment by alt227
> fresh air all day long thanks to hrv
This costs power and materials. Old houses dont require that. On a global scale, that increases power and manufacturing on a huge scale. Why are we throwing power and more modern materials at a problem that was solved in Roman times?
This would also reduce cost, helping the 'cheap' houses issue.
> On a global scale, that increases power and manufacturing on a huge scale. Why are we throwing power and more modern materials at a problem that was solved in Roman times?
Really?
A high quality modern balanced ventilator can ventilate an average sized house using 20-40W. That can supply over 100cfm and avoid around 90% of the conditioning that those 100cfm would otherwise require.
A good approximation is that 1 cfm at a 1 degree F temperature difference transfers 1.08 BTU/hr (sigh) or 0.317W of “sensible heat”. So, in a mild Mediterranean climate in the winter, heating by 30 degrees F, that 100cfm needs 0.317 times 3000 = 951W of sensible heat added.
So you can burn 951W of fuel. Or you can use 20-40W to get the same amount of fresh air but only need 95W to heat it. Or live in a climate with warm days and cool nights and require less thermal mass and therefore less material to moderate the temperature and avoid the need for active heating or cooling.
Without an HRV, either you don’t heat the building, or you ventilate less, or you use considerably more resources for temperature control.
Oh, and the device itself is two fans, a heat exchanger (fancy piece of plastic, generally), and some electronics and a box. Not exactly resource-intensive to build. And it can usually completely replace your bathroom fans if configured to do so, making it even less resource intensive.
In climates that require dehumidification or winter humidification, it’s more extreme because an ERV can exchange humidity (“recover latent heat”) too.